Brand / Model |
ELSIS; “ELS-0K7-CHR-V1” |
Manufacturer |
ELSIS A.S. |
Input Voltage Range |
85 – 265 Vac (Can be tailored to customer request) |
Input Power Factor |
>0,98 from half load to full load |
Input Current THD |
Less than 5% |
EMI Reflection to Input |
MIL-STD-461E, CE101, CE102 |
Input Circuit Breaker |
Sealed, T/M, DPST Toggle |
Output Voltage |
28 Vdc; one charge output with battery temperature compensation and two supply outputs with “+/-1%” stability |
Max. Continuous Output Power |
560 W |
Output Ripple |
Up to10 Mhz band, less than 200 mV |
Output Current Limit |
Fully electronic with 20% fold-back when 100% is exceeded |
Output Protection |
* Sealed, Thermal-Hydraulic, DPST toggle switch
* Electronic short-circuit protection for unlimited time
* Protection against reverse connection of battery (fuse)
* Prevention of battery discharge when charger is off |
Output Transient Protection |
MIL-STD-1275A |
Efficiency |
Better than 83% (from 50% to 100% load, under nominal conditions) |
Electromagnetic Compatibility |
MIL-STD-461E, CE101, CE102, RE101, RE102 |
Duration of Operation |
Continuous, 24 hours a day, 7 days a week |
Weight |
11 kg (apprx. 25 lb) |
Package Type |
Bottom screw mount, using metric “M6” screws |
Cooling |
Natural convection |
Mechanical Units |
Metric (can be modified to customer request) |
Dimensions |
W: 342 mm; H: 175 mm; D: 345 mm |
Operation Modes |
* “Charge” mode
* “Supply” mode
Selected on the front panel by screw-driver operated, sealed “Rotary Switch” |
Front Panel Controls, Indicators and Connections |
Input and Output Sealed Circuit Breakers (T/H),
“MS-38999” type circular connectors for AC In-Put, DC Out-Puts, LED’s for Charging, Full and Fault Indications |
Operation Temperature |
From –32o C to +63o C (with 10% degradation |
Storage Temperature |
From –40o C to +85o C |
Salt and Mist |
MIL-STD-810E Method 509.3, 48 hours mist and 48 hours dry time |
Mechanical Choke |
MIL-STD-810F |
Vibration |
MIL-STD-810F, Category-24 Procedure I Annex A 2.4.1 |
Acoustical Noise |
Less than 45 dB(A) |
Operation Altitude |
2000 m; above 2000 m according to degradation curve |
Relative Humidity |
Up to 90% (without condensation) |
Parallel Operation |
Parallel and load sharing operation of up to 4 units |